Project Metadata | Keywords | |||||||||||||||||||||||||||||||||||||||
|
|
This project is in support of the efforts by the Rather Creative Innovations
Group (RCIG) to apply the
MAGLEV2000™ technology to
the problem of energy storage.
Hartley Consulting supplies operational and economic analyses. It also supplies project planning, organizational advice and web design. RCIG is a small business created by Dr. John D. G. Rather in Oak Ridge, TN, to foster innovation in physics and engineering. MAGLEV 2000 was formed to develop and commercialize the revolutionary inventions of Dr. James Powell and Dr. Gordon Danby, who invented superconducting magnetic levitation vehicles. One result has been the creation of Sisyphus Energy, Inc., with John Rather as President and CEO and Dean Hartley as Vice President and COO. |
|
BACKGROUNDWe do not use electrical energy at a constant rate throughout the day and the electrical energy being supplied by the power grid must equal the amount being used. Because it is more cost-effective to produce energy at a constant rate, we would like to store energy during off-peak hours for use during peak usage. Currently, we are not able to do this in meaningful quantities. Figure 1 on the right, developed from data supplied by the U.S. Energy Information Agency (2011) and the International Energy Agency (2010), shows the average U.S. energy consumption/production by source and time of day (both Summer and Winter averages). The baseline is a production level between the low point and the high point of demand. For this data, it is about 400 gigawatts of energy.
As shown
in Figure 1, nuclear power represents a about 20% of baseline use. Hydropower
(from dams) and renewable sources (wind, solar, etc.) represent small fractions.
Coal represents about 50%. And natural gas supplies a small part of the baseline
needs. Nuclear power and coal are relatively inflexible sources. A nuclear
reactor needs to run at a constant temperature, producing a constant output.
Older coal-fired power plants have the same requirement. They can be shut down;
however, this is not something that can be done to adjust for hourly demand
changes. Some newer coal-fired power plants can reduce output by changing the
physical combustion point in boilers; however, this has only minor impact on
power output. Dams can spill water, rather than running it through the
generators, and can reduce flow rates; however, they also have constraints on
water level behind the dam and flow rates below the dam and depend on rainfall
levels. These factors mean that additional changes to meet varying hourly demand
levels are not popular with the operators. Renewable power depends on weather
and cannot be used for variable demand adjustments. Natural gas turbine plants
are capable of adjusting to hourly, daily and seasonal demands and are the main
source of such adjustments. However, shutting down any generating capacity
represents a waste of the capital used in creating the generating capacity. The section of the
figure labeled "Wasted baseline" represents generating capacity that is
not used because the demand is too low. The cumulative gigawatt hours of
power represented by this section comprises the most obvious opportunity
for better operating the energy supply. If this available energy is
captured and stored, then it can be used during the peak hours, reducing
the need for the total capacity during those hours - whether natural gas
or coal. Additions to the nuclear supply can reduce the need for
greenhouse gas producing power plants; however, this increases the
proportion of very inflexible energy generation. Having an energy
storage solution remedies this potential problem. |
|
The section of the figure labeled "Wasted baseline" represents generating capacity that is not used because the demand is too low. The cumulative gigawatt hours of power represented by this section comprises the most obvious opportunity for better management of the energy supply. If this available energy is captured and stored, then it can be used during the peak hours, reducing the need for the total capacity during those hours, specifically the capacity generated by natural gas or coal. On the other hand, there is a strong case for additional nuclear power for national energy independence and greenhouse gas reduction; however, the requirement for constant temperature operation would increase the amount of wasted energy during hours of off-peak demand. Having the very efficient Sisyphus energy storage solution completely remedies this problem. Calculating the value of a storage solution in detail is very difficult, as costs of capital, variability from day to day and season to season, etc., enter into the math. Further, these details differ over the various parts of the country. However, the problem of calculating this value becomes easier if the storage solution involved many local solutions in the same way that the entire power system involves local generating plants and demand areas. With this caveat, there is a simple proxy: the hourly cost of power. Power systems throughout the country have different rates that are charged to major customers (and in some cases, to residential customers). In general, the rates during off-peak hours are much lower than during peak hours. The proxy yields a simple formula: sum the energy price times the "wasted baseline" (at the local level) to yield a purchase cost. Then, sum the energy price during peak hours times the recovered energy (purchased energy quantity times the storage system efficiency factor) to yield a sales price. Subtract the purchase price from the sales price. As shown in Equation 1, if the result of these calculations is larger than the storage system cost, then the storage system saves money (or yields a profit). Equation 1. Profit Equation
|
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
ENERGY STORAGECurrently, we are not able to store energy in meaningful quantities. Figure 2 shows the global stored energy capacity by storage type (described later). Pumped hydro accounts for more than 99% of this capacity. The total U.S. electrical generation is about 1100 GW and the U.S. pumped hydro capacity is about 40 GW. Thus the U.S. energy storage capacity is only about 3.6% of the total generation capacity. Figure 3 helps explain this division. This figure (modified from an EPRI figure) shows the total capacities of each energy storage type (given the economic sizes of the systems) versus their discharge times. Certain uses require positioning in different areas of the figure. Uninterruptible Power Sources (UPS) require very quick discharge times and (generally) smaller power ratings. Support for load shifting within the power grid requires medium power ratings and variable discharge times. Bulk power management (the primary subject of this project) requires large power ratings and medium to large discharge times. System cost per MW is also a factor, but Figure 2 and Figure 3 do not address system cost. This will be discussed in the Power Source Comparisons section. Pumped hydro relies on the simple physics of potential energy: moving a mass away from the center of the earth requires energy, which is stored as potential energy (minus efficiency losses). Returning the mass to a lower level enables the recovery of this energy and conversion to electrical energy (minus efficiency losses). In pumped hydro systems, water is pumped at very high pressure into a much higher storage reservoir. This requires a large and costly dam with huge pumps. When the energy is required, the water is allowed to flow down through a turbine generator to recover the energy. The efficiency of pumped hydro (recovered energy/input energy) is about 70%. Compressed Air Energy Storage (CAES) also relies on simple physics: air is compressed into a chamber and then used to drive a generator to recover the energy. CAES has at least two major problems. The first is that compressing air also heats the compressed air. If this heat is lost prior to recovering the energy this results in an additional efficiency loss. The second problem is that for large scale uses, the air is compressed into a cavern, which is inherently dirty. The expanding air that drives the generator carries some of this dirt into the generating system. Flywheels are simply very massive wheels. Energy is stored by spinning the flywheel to higher revolutions per minute and recovered by using the rotation to drive a generator (reducing the speed). Superconducting Magnetic Energy Storage (SMES) stores energy as a direct current flow in a superconducting coil. As shown in the figure, SMES systems are capable of medium power ratings and have extremely short discharge times. They also have very high efficiency values, generally greater than 95%. Batteries of various types are also used for energy storage. Only those that have potential for large scale use are shown in Figure 3. Cost is a major factor for batteries since the power rating scales linearly with the required number of batteries. As the required number of batteries increases, the cost does also. Sisyphus, the subject of this proposal, addresses all of
the foregoing issues and provides superior solutions for the needs of national
and worldwide efficient energy management. This is represented in Figure 3 showing how Sisyphus
systems cover the ideal area for bulk power management. The sections below will
also demonstrate that Sisyphus can achieve these benefits at very favorable
costs. |
|
SISYPHUS OVERVIEWThe Sisyphus system for energy storage takes its name from the myth of Sisyphus, who was forced by the Greek gods to roll a massive boulder up a hill every day, only to have it roll back down during the night. He had to repeat this process forever. The Sisyphus energy storage system stores energy by transporting massive blocks uphill during off-peak hours (night rather than day) and recovers the energy by their return to the bottom during peak hours (day rather than night). The picture to the right (Figure 4) is Titian's painting of the myth, painted from 1548-1549. The Sisyphus system uses the same basic physics as the pumped hydro systems, storing electrical energy as potential energy and then converting that potential energy back into electrical energy. However, there are several important differences:
Further, like pumped hydro and
unlike
batteries, flywheels and SMES, the scaling cost of Sisyphus depends on
an increase of the low cost elements (concrete blocks), not on the
increase of the high cost elements. |
|
|
|
SISYPHUS TECHNOLOGYThe Sisyphus system for energy storage embodies several technologies, some simple and some complex. Operating TechnologiesAs shown in Figure 7 and Figure 8, the Sisyphus system is composed of several parts. There is a storage area at the low end of the system and a storage area at the upper end of the system. The concrete block masses are stored in these. There is a guideway connecting the two storage areas and vehicles that carry the blocks on the guideway, moving them from one storage area to the other. Not shown are the connections to the power grid, the power conditioning equipment and the electronic controls. Figure 7 shows the system in motor mode. Power is drawn from the grid to move the vehicles carrying the blocks from the lower storage area to the upper storage area, converting almost all of the electrical energy into recoverable gravitational potential energy. Vehicles are loaded from the lower storage area. Loaded vehicles move up the hill and deposit the blocks in the upper storage area. Empty vehicles move down the hill to get more blocks. The system is operated in this mode during off-peak hours when the energy cost is low and proceeds until all of the blocks are moved up hill. Figure 8 shows the system in generator mode. The blocks from the upper storage area are loaded onto vehicles, which then slide down the hill, converting almost all of the potential energy into electrical energy. Loaded vehicles deposit the blocks at the lower storage area and move up the hill to get more blocks. The system is operated in this mode during peak hours when the energy can be sold at the highest price and proceeds until all of the blocks are moved down the hill. |
|
Motor/Generator TechnologiesThe levitation/motor/generator system consists of two components, the superconducting quadrupole component and the non-superconducting aluminum coils. The quadrupole component contains four coils of superconducting wire that support an enormous lossless current. As long as the coils are maintained at the necessary low temperatures, these currents generate extremely strong magnetic fields. These fields interact with the aluminum coils, inducing currents and opposing magnetic fields. The magnetic fields play two roles: levitation and propulsion / power generation effects. The interactions of these fields create the magnetic levitation effect, keeping the vehicle several centimeters above the guideway. The levitation may be supplemented by adding iron plates to the top of the guideway beam. Figure 12 is a CAD/CAM perspective view of the quadrupole component,
showing the four containment boxes and the cooling connections running between the
pairs. The superconducting coils are in the containment boxes that keep the
loops in a superconducting state and the cooling apparatus that maintains the
temperature of the containment boxes is the long box between them. Looking at
the side, the two loops have currents circulating in opposite directions, so
that the flow where the vertical parts are closest is in the same direction (up
or down) for the two loops. |
|
Figure 13 is a schematic of the aluminum coils contained in the guideway panels.
Figure 15 is a photograph of a set of aluminum coils prior to being encased in
polymer concrete to fabricate the panel. |
|
Intellectual Property and Magnetic Levitation ApplicationsJames R. Powell and Gordon T. Danby created and patented a number of inventions in the field of superconducting magnetic levitation. Powell and Danby presented their original concepts in 1966 and received a patent in 1968. The original concept used low temperature superconducting (LTS) magnets (cooled with liquid helium). In 2000, they were awarded the Benjamin Franklin Medal in Engineering by the Franklin Institute for their work. Powell and Danby later improved their concept by using quadrupole superconducting magnets, rather than dipole magnets. The original quadrupole magnets are also LTS magnets; however, newer designs use high temperature superconducting (HTS) magnets (cooled with liquid nitrogen). Relevant patents for Sisyphus are listed in Table 1 below. Table 1. Intellectual Property Patents
Starting in 1969 the Germans built a magnetic levitation transportation system using non-superconducting magnets. By 1993 they achieved 450 km/hour speeds. The separation between the vehicle and the guideway must be constantly monitored and corrected due to the unstable nature of electromagnetic attraction. The system's inherent instability and the required constant corrections by outside systems may induce vibration. This system requires very costly guideways because the magnets are weak (~1 cm gaps) and has no ability for track switching. This system is in use in Shanghai, China. Starting in 1972 the Japanese built a magnetic levitation transportation system using Powell and Danby's original concept. By 1997 they achieved 550 km/hour speeds. Strong magnetic fields (from the dipole superconducting magnets) on the train require the use of magnetic shielding to protect passengers with pacemakers and magnetic data storage media such as hard drives and credit cards. The superconducting magnets do allow greater gaps between the magnets and the guideway; however, the guideways for this system are very costly. Track switching is possible, but difficult. While the Sisyphus system is not designed for passengers, it may use quadrupole superconducting magnets, which do not require shielding to prevent untoward effects on nearby systems. Also under investigation is the cost differential between LTS systems and HTS systems. The HTS wire is currently more expensive than the LTS wire; however, it is expected that the use of liquid nitrogen cooling will be much more robust than cooling with liquid helium, which will provide cost savings in the design. The Sisyphus system supports gaps between the magnets and the guideway of about 10 centimeters. The quadrupole option supports high-speed electronic switching. The prefabricated guideway beams are inexpensive (compared to the Japanese system).
|
|
SISYPHUS IMPLEMENTATIONThe implementation can be divided into four parts, the physical definition of the system, the costs of the system, the projected financial results, and the implementation phasing. Physical DefinitionFigure 16 shows a view of the proposed site for the demonstration Sisyphus system. The line between the yellow pins is the TVA right of way for power line down from the wind farm on top of Buffalo Mountain. The lower storage yard will be sited at the lower yellow pin. The upper storage yard will be sited in the flat area below the upper storage pin. Figure 17 shows a schematic perspective view of the system, showing the relative sizes of the storage yards and the guideway linking them. |
|
|
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
The demonstration Sisyphus system has a nominal energy storage rating of 200 megawatt hours (MWH). That is 200 MWH are stored by the system. With an efficiency rating of >90%, this means that ~180 MWH will be recovered. The storage rating is defined by physical parameters of system height (640 m), weight per block (100 metric tons), and number of blocks moved (1148). The potential energy stored in one 100 metric ton block raised 640 m is 0.1742 MWH. Lifting 1148 blocks stores 200 MWH. Keeping 1148 blocks alternately at the foot of the grade and the top of the grade requires two storage yards of ~3.2 acres, each. The layout also requires ~6300 m of guideway. Vehicles will move at ~60 miles per hour between the storage yards. Higher speeds are easily possible; however, efficiency losses from increased wind drag reduce the value of higher speeds. It will take the vehicles 14 seconds to reach 60 mph and 14 seconds to decelerate. With an estimated 50 seconds to load a block and 50 seconds to unload it, the total round trip time is about 4 minutes. In order to lift all 1148 blocks during the off-peak hours, 12 vehicles are required ((4 min x 1148 blocks / 12 vehicles) / 60 min/hour = 6.4 hours). Because the peak time is longer than 6.4 hours, the rate of energy recovery can be varied from rapid to slow, depending on needs. In addition to the vehicles, guideway, and blocks, the storage areas will need handling equipment and the entire system requires electrical control and power conditioning subsystems. This Sisyphus system requires no investment in land, as the TVA right of way is sufficient to contain the system. Upon the successful completion of the demonstration system, the entire system can be upgraded to a nominal 1000 MWH of storage. This five-fold increase in storage requires five times as many blocks (5740) and 7 1/3 times as much block storage (23.5 acres per storage yard) [to minimize guideway changes]. However, it only requires 3 1/3 times as many vehicles (40), which comprise the most expensive part of the system, and 1 1/4 times as much guideway (~8020 m) [to account for the increased storage area], which is a moderately expensive part of the system. |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
System CostsThe system costs are divided into investment costs to build the system and annual costs for its operation, as shown in Table 2. The total investment cost of $60 million is based on current best estimates of costs of the various components of the system. This figure also shows up as a 30 year straight-line amortization in the annual costs. The cost of purchased energy is based on an estimate of 8 cents per KWH ($80/MWH) for energy purchased off-peak. Table 2. Demonstration System Costs
These cost estimates are based on the assumption of multi-unit production.
The first Sisyphus system will incur additional setup costs, which are described
in the implementation phasing section below. |
|
Projected Financial ResultsThe financial results are divided into gross revenue (delivered energy times price), net revenue (gross revenue minus energy purchase costs and operations & maintenance costs), and profit (net revenue minus amortization costs), as shown in Table 3. The price of energy sold is based on an estimate of 20 cents per KWH ($200/MWH) for energy sold at peak prices. The quantity of energy delivered is 90% of the quantity purchased. The Return on Investment (ROI) is the Net Revenue as a percent of Total Investment. Table 3. Projected Demonstration System Financial Results
|
|
1000 MWH Upgraded System FinancialsThe financial results for the upgraded system are shown in the same formats as for the demonstration system (Table 4 and Table 5). Note that the Investment figures are totals for building this system and include the costs for the demonstration system. The increase in profitability is due to the efficiency of scale, as the energy costs and sales come to dominate the other costs. Table 4. 1000 MWH System Costs
Table 5. Projected 1000 MWH System Financial Results
|
|
Implementation PhasingThe creation of the first Sisyphus system, the demonstration system on Buffalo Mountain, TN, requires additional setup costs. These setup costs involve creating engineering drawings and tooling and extensive testing to establish the workability of the concepts and refine the costs. Workability will be defined by the Technology Readiness Level (TRL) metrics. The work will proceed in six phases, as shown in Table 6. Each phase has short definition and a goal describing what will be achieved during the phase. For each phase of the demonstration system, the estimated labor and material costs are shown, along with the total cost for the phase and the phase duration. The totals for all phases of the demonstration system are also shown. The estimated total cost and time to upgrade the system to the 1000 MWH Sisyphus system are shown as Phase 5. Table 6. Sisyphus Phases
|
|
Table 7, below, compares the costs of electrical energy among several options. The numbers in the table must be regarded as approximate for several reasons. First, actual power plants are based at a particular location, have a particular design, and are built at a particular time. Therefore, their actual costs are unique. The numbers in the table are “average” numbers, where the proper weightings to produce the averages are debatable. Second, the numbers are derived from several sources and may contain hidden assumptions that differ among the sources. Third, each type of power source has its own constraints, making comparisons difficult. For example, hydro-electric plants must be built on rivers with particular characteristics and all or almost all of those situations may have already been used. Fourth, some numbers are estimates, with unknown accuracy values. This is particularly true of the Sisyphus numbers and the O&M costs for pumped hydro storage. Nevertheless, the table gives a clear overview of the situation, as long as there is unused energy available for storage, building and using a Sisyphus system is less expensive than building a new power generating system of any type, except perhaps hydro-electric. It is also less expensive as a replacement power source (comparing operating expenses) than any source other than hydro-electric.
Table 7. Comparison of Power Source Costs in $/MWH
Type | O&M | Fuel | Subtotal | Capital Cost/ Delivered MWH | 30 yr Ammor-tization | Total | Other Estimate |
Fossil Steam | 8.86 | 28.34 | 37.20 | 1441.90 | 48.06 | 85.26 | 121.50 |
Gas Turbine | 5.22 | 30.45 | 35.67 | 304.27 | 10.14 | 45.81 | 85.05 |
Hydro-electric | 11.34 | 0.00 | 11.34 | 364.30 | 12.14 | 23.48 | 84.50 |
Nuclear | 19.81 | 7.61 | 27.42 | 1933.16 | 64.44 | 91.86 | 96.10 |
Pumped Hydro Storage | 43.12 | 0.00 | 43.12 | 862.36 | 28.75 | 71.87 | |
Sisyphus (1000 MWH) | 24.86 | 0.00 | 24.86 | 497.18 | 16.57 | 41.43 |
The sources for the O&M, Fuel, and Capital Costs are from US Energy Information Administration (EIA) 2012 reports, with the Capital Cost/Delivered MWH calculated using EIA efficiency values. The Pumped Hydro Storage O&M costs, however, are calculated as 5% of the total Capital Costs for the system, using the same percentage as is used for the Sisyphus estimate. The Sisyphus numbers come from the estimates shown above. The Other Estimate values come from a Wikipedia article on levelized costs in 2012 dollars of electricity by source. The differences in these estimates for Fossil Steam, Hydro-electric, and Nuclear lie in the estimates of capital costs, while the difference for Gas Turbine come from both capital costs and O&M plus Fuel costs. It should be noted that both Hydro-electric and Pumped Hydro Storage have severe location constraints and that both Pumped Hydro Storage and Sisyphus assume that there is excess power to be stored, as neither actually generate new power.
The use of Sisyphus systems has two additional major implications: enhanced grid security and support for rapid local load balancing.
Sisyphus systems are capable of storing commercially significant amounts of power. The 1000 MWH upgraded system described here moves fewer than 6000 blocks up 640 m, requires about 50 acres of land, and costs less than $200 million. There are untold numbers of sites in the U.S. that can accommodate such a system. Sites with larger elevation differences and those using more blocks can store more power. A great number of these sites will be found near power generation sites, meaning that the local area will be less dependent on grid stabilization from out of the local area.
Currently, the U.S. is divided into 3 major power grid sectors and numerous subsectors. However, even the subsectors are quite large. The interconnections are built to limit blackouts from affecting too many other areas; however, the 2003 Northeast blackout affected about 45 million people in the US and 10 million people in Canada. Sisyphus will enable smaller sectors to handle problems, preventing large scale blackouts, whether caused by natural disasters or by cyber attacks.
Rapid Load BalancingIn the physical description of Sisyphus above, the top speed of the vehicles was set at 60 mph and the trip time to load a block, travel to the other storage yard, and unload a block was calculated as 4 minutes. This resulted in a minimum time to move all the blocks from one storage yard to the other of 6.4 hours (for the 200 MWH demonstration system). Given 90% efficiency, 180 MWH would be recovered in 6.4 hours, yielding an average power rating of ~28 megawatts. However, some local situations might require more power for load balancing. Increasing the vehicle speeds would yield lower trip times and produce more power; however, the power peaks at 90 mph and decreases after that due to the ratio of acceleration time and time traveling at maximum speed. These calculations assume constant efficiency, but efficiency will decrease with increasing speed due to wind resistance. Even without wind resistance increase, the amount of power increase from 60 to 90 mph is only about 4%. Increasing vehicle frequencies will also yield more power. The 6.4 hour time assumes that subsequent vehicles start loading about 20 seconds after the previous vehicle starts loading. The 12 vehicles could be set to start loading about 10 seconds after the previous vehicle started, giving a 60% increase in power during the time for the 12 vehicles to descend; however, the vehicles would have to return to the top, with no power being recovered during the interim. Figure 27 graphs the power (green curve) generated by 12 vehicles for different separation times (measured on the left axis). It also shows the lag time (bent straight line) before the first vehicle (calculated as the 13th vehicle) can start generating power again. As the separation time is reduced to about 20 seconds, this curve (measured on the right axis) drops because the only gaps between vehicles are the separation times. However, separation times less than 20 seconds require that the available 12 vehicles bunch up, leaving larger and larger gaps between the bunch of 12 vehicles. The implication of these calculations is that Sisyphus can generate bursts of power over short time frames. However, such a burst of power must be paid for with a delay until more power can be produced. As shown in Figure 27, with all 12 vehicles running in a single bunch (zero seconds separation), the maximum power is generated at a cost of maximum recovery time (240 seconds = 4 minutes) |
|
As the U.S. moves away from fossil fuel generated electrical energy, the need to store energy during off-peak periods for use during peak periods will increase. Done properly, storing this energy does not increase the overall cost of energy, rather it enables cost savings.
Sisyphus is a system for storing and recovering electrical energy. Sisyphus stores the energy by moving massive blocks from a low point to a high point, converting the electrical energy into potential energy. It recovers the energy by moving the blocks from the high point to the low point, converting the potential energy back into electrical energy. Because it uses superconducting magnets to move the blocks, it has an efficiency of greater than 90%. To store more energy, Sisyphus only needs to move more blocks, which are inexpensive. This means that it scales well, costing less per megawatt hour (MWH) stored as the system size increases. Sisyphus systems can be built anywhere that has a significant height differential (>600 m), with slopes from 25% grade to vertical (including mine shafts). That means that Sisyphus systems can be built almost anywhere in the U.S. and will deliver locally useful amounts of stored energy (1000 MWH and up).
Sisyphus systems can be built at a lower cost than creating new power plants or running existing power plants for peak-demand use. Fossil fuel plants that generate greenhouse gases can be phased out without worrying about the problem of varying electric power demands. Alternative power sources, such as wind and solar that do not supply constant power, will generate power when feasible for use when needed.
Because the Sisyphus system supports variable energy recovery rates, it can surge its energy recovery to support rapid local load balancing. In addition, Sisyphus’ local energy storage will support smaller grid segmentation, which will make the power grid much more secure against failures and hostile attacks.
The Sisyphus concept is a transformative improvement of an earlier generation American magnetic levitation technology that is in commercial development in Japan. The patented improvements have been tested at the component level and will be tested at the system level during the project to build a 200 MWH demonstration system. This system developed by this proposal will then be upgraded to a commercial 1000 MWH system.
Sisyphus is the solution to these acute problems, providing a vital missing element in the national and international quest for higher energy efficiency, greater security and lower greenhouse gas emissions.
If you arrived here using a keyword shortcut, you may use your browser's "back" key to return to the keyword distribution page.
Return to Hartley's Projects Page